In a nutshell, a fog system (atomizing humidifier) is high-pressure RO water atomized through misting nozzles. These systems are relatively simple, but an improper design can have major consequences. In this series, we share the most common design mistakes and how to avoid them. Part 2 covers the evaporative cooling effect.
How does a reverse osmosis system work?
You might think it's unlikely that anyone would undersize a water treatment system, but it happens more often than you'd expect.
Reverse osmosis works by pressurizing the source water and passing it through a semi-permeable membrane that removes 98–99% of the dissolved solids. Typically, for every gallon of feed water:
- about 65% goes to the humidifier as permeate (RO-quality water), and
- about 35% goes to drain as concentrated mineral water.
This ratio varies with system size and manufacturer, so review the data sheets for your specific equipment.
Why does cold feed water reduce RO output?
Once you know the manufacturer's rating, calculating permeate output looks simple. But water temperature has a large effect on RO performance. Colder water is more viscous and passes through the membrane more slowly, so output drops as the feed water temperature falls.
Read the fine print on the data sheets and you'll see that output is usually rated at 77°F feed water, which gives the 65/35 split above. A system designed to supply a humidifier through the winter is more likely to see feed water at 50°F or less. At 50°F, you must apply a 0.68 temperature correction factor to the permeate:
Correction factor × permeate at 77°F = actual output
For example, an RO system rated at 1,000 gallons per day (GPD) at 77°F will produce only about 680 GPD with 50°F feed water.
Also keep in mind that RO system efficiency begins to decline from the moment the system starts up, so the design needs margin for that as well.
How should you size water treatment for a winter humidification load?
- Temper the feed water where possible. It's recommended to use a hot water/cold water blending valve to bring feed water to a more reasonable 55–70°F, then apply the correction factor for that temperature.
- If tempering isn't an option, design for winter water. Size the RO system for the coldest expected feed water temperature, not the 77°F rating.
- Allow for declining efficiency. Account for the drop in output that occurs as the system operates.
Undersize the RO and the humidifier runs short of water on the coldest, driest days of the year, when humidification demand peaks.
GoFog sends a water sample to an independent lab for analysis before each system is installed and provides the right water treatment equipment, from simple cartridge filtration to RO systems with outputs from 500 to 29,000 gallons per day. See the GoFog Water Treatment Selection guide (PDF) for model data.