How much heat does evaporating water absorb?
The energy-saving potential of atomizing humidifiers, with their small-horsepower pump units, is well documented. The additional free cooling that occurs during evaporation is often overlooked.
Two properties of water explain it:
- Latent heat is the heat one pound of water absorbs when it changes from liquid to vapor. It is about 970 BTU/lb at atmospheric pressure, starting from water at 212°F.
- Specific heat is the energy needed to raise one pound of water by 1°F, which is 1 BTU/lb.
For room-temperature water at 70°F, the calculation is:
| Step | Energy |
|---|---|
| Raise the water from 70°F to 212°F (142°F × 1 BTU/lb·°F) | 142 BTU |
| Change from liquid to vapor (latent heat) | 970 BTU |
| Total to fully evaporate 1 lb by atomizing with a fog system | 1,112 BTU |
Most of the energy goes into the change of state, so the initial water temperature has little effect on the overall cooling. In practice, fog droplets evaporate at the air's wet-bulb temperature rather than at boiling, where latent heat is slightly higher (about 1,060 BTU/lb near 60°F), so the total lands in the same range.
How does evaporative cooling help inside an air handling unit?
When fogging inside an air handling unit, the evaporative cooling is often beneficial. During the heating season, the free cooling reduces the amount of cold outside air the air-side economizer brings in, which in turn reduces the humidifier load and water usage. (See How to Humidify an Air-Side Economizer.)
In the cooling season, the same fog system can act as a direct evaporative cooler, modulating to stay below the building's maximum allowable relative humidity.
Why is the benefit greater in manufacturing plants?
When fogging directly in the space in manufacturing facilities, the benefit of evaporative cooling is even greater. Many manufacturers have high internal heat loads, and some must cool year-round, so the free cooling from a fog system adds up to significant energy savings.
Worked example:
- Fog system capacity: 1,000 lbs/hr
- Operating hours: 3,000 per year
- Free cooling: 1,000 lbs/hr × 3,000 hr × 1,112 BTU/lb ≈ 3.3 billion BTU per year (about 278,000 ton-hours)
- Utility rate: $0.15/kWh
- Estimated savings: more than $30,000 per year
This is another reason fogging is common in manufacturing buildings, and why steam is not a practical option for humidifying large open spaces. For dedicated cooling applications, see evaporative cooling systems.