Harvard University Science and Engineering Complex: Lab Humidification and Evaporative Precooling

GoFog supplied the high-pressure fog humidification system for Harvard University's 530,000-square-foot Science and Engineering Complex. A single redundant pump skid of less than 10 HP delivers more than 10 GPM (5,000 lbs/hr) of reverse osmosis water at 1,000 psi to humidify the building's laboratories in winter, and the same skid provides indirect evaporative precooling in summer.

GoFog, Inc. Press Releases Published Updated September 2026 3 min read

Architectural rendering of Harvard University's Science and Engineering Complex, a large multi-story building with a metal screen facade and pedestrians in the foreground

About the project

At the time of this 2019 announcement, the 530,000-square-foot Science and Engineering Complex was set to open in 2020. It was designed to house approximately two-thirds of Harvard's John A. Paulson School of Engineering and Applied Sciences (SEAS) and to be among the most advanced facilities of its kind in the world.

GoFog, which specializes in custom high-pressure atomizing humidifiers, was selected as the basis of design to help create a system that maintains the various relative humidity requirements throughout the building's laboratories. GoFog was later awarded the contract to supply the system.

How does the fog system humidify the laboratories?

The building introduces more than 300,000 CFM of outside air through multiple air handling units (AHUs). The GoFog system serves them all from one central plant:

  • One fog pump skid in the basement mechanical room feeds more than 10 GPM (5,000 lbs/hr) of reverse osmosis water at 1,000 psi.
  • Motorized ball valves mounted near each AHU admit high-pressure water to the fog nozzle manifolds inside the AHUs.
  • BMS staging: the valves are staged by a demand signal from the building management system.
  • Redundancy: the skid has two pumps that operate as alternating duty/standby, which makes a highly efficient redundant system that uses less than 10 HP.

For more detail on the equipment, see Humidity Control Simplified: Valve Staging Racks and High Availability Fog Systems. For other laboratory projects, see healthcare and laboratory humidification.

How does the same system cut summer cooling loads?

Besides humidifying the labs during winter and the transitional seasons, the same pump skid is used in the summer to make the building's HVAC system more efficient. It provides indirect evaporative cooling for the supply air entering the building.

  1. Fogging the exhaust air. A secondary set of fog nozzle manifolds inside the exhaust units saturates the exhausted room air before it enters an energy recovery coil (ERC).
  2. Sensible energy recovery. The energy recovery system has one coil in the exhaust airstream and a second coil in the supply airstream. It transfers a portion of the cooling from the lab exhaust air to the supply side.
  3. Precooling without moisture. This sensible transfer precools the hot outside air entering the supply AHUs without adding any unwanted moisture.

Fogging in the exhaust section increases the cooling effect by more than 10°F. The cost impact is minimal because the high-pressure pump skid is already in place and would otherwise sit idle during humid Massachusetts summers.

Could a GoFog system work for your building?

Contact GoFog or speak directly with an expert at (803) 220-0101.

02FAQ

Frequently asked questions

How does one fog pump skid serve multiple air handling units?

A single skid in the basement mechanical room supplies 1,000 psi reverse osmosis water to motorized ball valves mounted near each AHU. The valves open the fog nozzle manifolds inside each AHU in stages, based on a demand signal from the building management system.

How is the same fog system used in summer?

A secondary set of fog manifolds in the exhaust units saturates the exhaust air before it reaches an energy recovery coil. The cooler exhaust air increases the sensible precooling of the outside air entering the supply AHUs by more than 10°F without adding moisture to the supply air.