What is the problem with humidifying economizer air?
When the weather cools, many non-residential buildings use air-side economizers to provide "free cooling": bringing in cool outside air through the HVAC system instead of running mechanical cooling. The benefit is obvious, but cool outside air holds little moisture, which makes it hard to maintain indoor humidity levels.
The conventional fix is a steam humidifier. However, steam requires approximately 1,000 BTU of energy to evaporate just 1 lb of water. That energy use can offset most or all of the savings the economizer provides. As a result, many building operators disable the economizer and mechanically cool the return air rather than run the boiler for humidification. It's the lesser of two evils, and it simplifies the sequence of operation, but it gives up the free cooling.

Select the chart to open the full-size GoFog psychrometric chart (PDF).
How does an atomizing humidifier use less energy than steam?
An atomizing humidifier still needs about 1,000 BTU to evaporate 1 lb of water. The energy has to come from somewhere. The difference is where it comes from.
A GoFog atomizing humidifier sprays very fine water droplets into the airstream, and the heat already in the air evaporates them. The only purchased energy goes to the high-pressure pump unit, which uses less than 0.003 kW per pound of water evaporated. That's roughly 1% of the energy a steam humidifier consumes.
What does this look like on a psychrometric chart?
The GoFog psychrometric chart above plots an example economizer day in Boston, Massachusetts:
- Outside air: 55°F at 30% RH
- Desired room condition: 72°F at 40% RH
- Desired supply air temperature: 55°F
With a steam humidifier, the economizer would run at or near 100% outside air, and the humidifier load would be approximately double that of an adiabatic humidifier. With the adiabatic (fog) system, the economizer adjusts to approximately 50% outside air because of the evaporative cooling. Because less outside air comes in, the humidifier load is reduced too.
How does the economizer handle the evaporative cooling effect?
As the atomizing humidifier evaporatively cools the air, the economizer automatically compensates by reducing the amount of outside air and increasing the amount of return air to hold its supply air setpoint. Because less dry outside air comes in, the humidification load also drops.
The result is a system that:
- keeps the economizer running and captures its full free-cooling savings,
- maintains the desired relative humidity, and
- uses less water, because the humidifier only treats the reduced volume of outside air.
This is why buildings with air-side economizers, including data centers, are among the ideal applications for a fog system. For 100% outside air (make-up air) units, where no return air is available to offset the cooling, see Fog System Design Blunders: Part 2.
Get a design for your air handlers
GoFog can review your air handler sequence and provide a humidifier design, equipment selection and energy analysis. Contact GoFog or call (803) 220-0101.