What if the AHU doesn't have enough evaporative distance?
Installing an atomizing humidifier inside an air handling unit (AHU) can be difficult if there isn't enough room for optimal evaporative distance: the distance the atomized water droplets travel from the nozzles to the mist eliminators. An atomizing humidifier section normally requires 3–6 ft of evaporative distance.
If that space isn't available, the solution is simpler than you might think: install the nozzle manifolds and mist eliminators in a modified section of ductwork.
How is a duct mounted humidifier section designed?
- Enlarged cross-section. The section is enlarged to slow the air velocity to approximately 500 FPM, giving most of the atomized water droplets enough time to evaporate.
- Stainless steel, watertight construction. Because it is a wet section, it must be built from stainless steel and be completely watertight.
- Mist eliminators. Mist eliminators at the downstream end capture any droplets that haven't evaporated. See the mist eliminator specification (PDF).
Why use a factory-built section instead of building one on site?
In the past, these duct sections were built by local contractors, and the nozzle manifolds and mist eliminators were installed on site. That approach requires detailed drawings and close coordination to make sure everything is built and installed correctly, which leaves room for error.
GoFog simplifies the process by manufacturing custom humidifier duct sections with the nozzle manifolds and mist eliminators pre-installed at the factory. Each section has:
- heavy-gauge stainless steel construction
- fully welded seams
- a sloped drip pan and drain
- a watertight access panel
- duct flanges on each end
- nozzle manifold connections that already penetrate the factory-sealed section
How is a GoFog duct section installed?
- The completed section ships to the project site ready to install.
- The contractor adds transitions to and from the existing ductwork.
- The contractor insulates the outside of the section.
- The piping from the humidifier pump system is connected to the nozzle manifolds.
Output can then be staged from the BMS with a valve staging rack, just as it would for manifolds inside an AHU. Learn more about commercial humidification.
Request a design
GoFog offers a free design and quotation for duct mounted humidifier sections. Contact GoFog or speak with an expert at (803) 220-0101.