How does a valve staging rack control a fog humidifier?
The atomizing nozzles inside each AHU are controlled by an external panel that contains a PLC and staging valves. The panel modulates the humidifier output based on a demand signal from the building management system (BMS), either 0–10V or 4–20mA.
When the BMS demand signal is high enough to open the first stage, the valve panel sends a pump request to the fog pump station. The pump then supplies 1,000 psi reverse osmosis water to the nozzles.

How do four valves create 15 stages of control?
The valve rack shown here uses four motorized 3-way ball valves. Each valve's discharge port feeds a manifold inside the AHU, and each manifold has a different number of nozzles. By opening the valves in different combinations, the PLC produces 15 distinct stages of capacity control, so humidifier output can closely match the BMS demand.
What features are built into GoFog staging racks?
- Programmable stage up/down time delays prevent valve cycling.
- An automatic flush cycle keeps fresh water in the system.
- Optional inputs accept a high limit sensor and an air proving switch.
- Pre-piped and pre-wired, which simplifies installation for the mechanical contractor.
- Factory tested as a complete unit.
- Motorized ball valves instead of solenoid valves for quiet operation.
Where are staging racks used?
One pump skid can serve staging racks on many air handlers. At the Harvard University Science and Engineering Complex, a single redundant high availability pump skid feeds motorized ball valves mounted near each AHU, each staged by the BMS. To match the panel to your site's controls standards, see GoFog Humidity Control.