Skip to content
Call (803) 220-0101
3625 Centre Circle, Ste C
Fort Mill, SC 29715

04News & Insights

The Ideal Fog System Application: Where High-Pressure Fogging Works Best

High-pressure fog systems have been used for decades on a wide range of projects, but five applications stand out: laboratories, manufacturing plants, data centers, any building with an air-side economizer, and agriculture. Each can use waste heat or free cooling to make fogging exceptionally energy efficient.

GoFog, Inc. Insights Published Updated September 2026 3 min read

Cutaway illustration of an air handling unit showing airflow through the filter, coils and supply fan, with fog in the humidification section between the coils

Why are laboratories ideal for fog systems?

Laboratory HVAC systems typically use multiple make-up air units (MAUs). A single fog system pump unit can humidify all of those air handlers, which greatly reduces capital cost. A secondary pump can provide redundancy where required.

Labs usually have energy recovery coils (ERCs), which help offset some of the evaporative cooling that occurs when the fog system is running. An additional set of fog nozzle manifolds can also be placed just upstream of the exhaust recovery coils. These evaporatively cool the exhaust air to near saturation, providing an additional 10°F or more of precooling during the summer months, when the fog system pump would not normally be running. The Harvard University Science and Engineering Complex uses this approach. Learn more about laboratory and healthcare humidification.

Why does fogging suit manufacturing plants?

Printing, woodworking and textile plants are a few of the many manufacturers that need humidity control for product stability and static control. In these buildings, fog nozzle manifolds are installed directly in the space at ceiling level and run the length of the building above the aisles.

Fogging directly in the space provides the required humidity control and uses the waste heat that collects at the ceiling to evaporate the fog droplets. This approach can humidify an entire manufacturing plant with a fog system pump of less than 5 HP. See manufacturing humidification.

Why use fog instead of steam in a data center?

Static control is vital in a data center, and maintaining the proper humidity level plays a key role in achieving it. Servers produce a large amount of excess heat, so it makes sense to use that waste energy wherever possible, rather than install a steam boiler to raise the relative humidity.

A fog system paired with an air-side economizer uses a portion of the server heat to offset the cooling effect that occurs when fog droplets evaporate. Because a fog system requires less than 0.003 kW per pound of water evaporated, it provides precise humidity control while lowering the facility's power usage effectiveness (PUE). See data center humidification.

Why is any building with an air-side economizer a good fit?

Most commercial buildings use air-side economizers to provide free cooling during the transitional seasons. This is a textbook application for fogging.

As moisture is added, the heat in the return air offsets the evaporative cooling effect. The supply air temperature sensor modulates the mix of return and outside air as the fog system stages up and down to maintain humidity in the space.

Because the fog system also provides free cooling, the economizer brings in much less outside air. The humidifier load depends mostly on how much dry outside air enters the building, so it is smaller with fog than with steam. The fog system uses less water and runs at a fraction of the cost of a traditional steam boiler. For a full explanation, read How to Humidify an Air-Side Economizer.

Why do greenhouses and botanical gardens use fog?

Designing a greenhouse, conservatory or botanical garden involves many decisions. Near the top of the list is how to cool and humidify the space while managing maintenance and energy use. A fog system is a common choice because it addresses all three.

Each GoFog system is custom engineered to the client's needs. The tiny fog droplets evaporate quickly, creating an ideal growing environment without wetting the plants. This increases production, reduces waste and improves product quality, all with very little energy and minimal maintenance.

Is your project a good fit for fog?

GoFog will review your application and provide a custom design, equipment selection and energy analysis. Contact GoFog or call (803) 220-0101.

02FAQ

Frequently asked questions

Can one fog pump unit humidify several air handlers?

Yes. In laboratories with multiple make-up air units, a single high-pressure pump unit can feed fog manifolds in all of the air handlers, and a secondary pump can be added for redundancy.

How large a pump does a manufacturing plant need for in-space fogging?

Because nozzle manifolds at ceiling level use waste heat to evaporate the droplets, a fog system pump of less than 5 HP can humidify an entire manufacturing plant.

Can a humidification fog system also provide cooling in summer?

Yes. In labs with energy recovery coils, an extra set of fog manifolds upstream of the exhaust recovery coil can evaporatively cool the exhaust air to near saturation, providing 10°F or more of supply air precooling using the same pump.

Have a project in mind?

GoFog engineers will review your application and provide a custom design and free quote.